Overview of Functional Blocks
Date: 2026-10-21
Dictionary Version: 138
Mac Version: 101
This page lists the Functional Blocks available in the KNX information model (KIM) to provide an overview of the functionality descriptions provided by KNX.
For each Functional Block, it states its:
- ID, for example 321
- name, for example Room Temperature Sensor
- identifier (IRI), for example knx:fb.321
- abbreviation, for example RTS
- reference specification, for example Defined in: Ch. 7/19/20 §3.1
- list of datapoints ('DPAs') with further information, for example knx:dpa.321.51
FB 100: Room Setpoint Manager HVAC-Mode Driven
knx:fb.100 [RSMHD]
Defined in: Ch. 7/10/4 §3.4 (KNX Standard v3.0.4)
(NOTE: This Functional Block is in 'beta' status and may be subject to changes)
| DPA | Desc | Direction | Mandatory | DPT |
|---|---|---|---|---|
| knx:dpa.100.51 | HVACModeEff | Output | O | knx:hvacMode |
| knx:dpa.100.52 | HVACModeEffNext | Output | O | knx:hvacModeNext |
| knx:dpa.100.53 | TempRoomSetpSetHeatEff | Output | O | knx:tempRoomSetpSet_a4a_ |
| knx:dpa.100.54 | TempRoomSetpSetCoolEff | Output | O | knx:tempRoomSetpSet_a4a_ |
| knx:dpa.100.55 | TempRoomSetpHeatEff | Output | O | knx:valueTemp |
| knx:dpa.100.56 | TempRoomSetpCoolEff | Output | O | knx:valueTemp |
| knx:dpa.100.57 | HVACModeUserEff | Output | O | knx:hvacMode |
| knx:dpa.100.58 | TempRoomSetpUserOffsetEff | Output | O | knx:valueTempD |
| knx:dpa.100.59 | TempRoomSetpUserAbsEff | Output | O | knx:valueTemp |
| knx:dpa.100.60 | ComfortProlongEff | Output | O | knx:state |
| knx:dpa.115.62 | TempRoomSetpSetHeatShift | Input | O | knx:tempRoomSetpSet_a3a_ |
| knx:dpa.115.63 | TempRoomSetpSetCoolShift | Input | O | knx:tempRoomSetpSet_a3a_ |
| knx:dpa.121.51 | TempRoomSetpTariffShift | Input | O | knx:valueTempD |
| knx:dpa.121.52 | TempRoomSetpLoadShedShift | Input | O | knx:valueTempD |
| knx:dpa.343.51 | WindowStatus | Input | O | knx:windowDoor |
| knx:dpa.384.51 | TempRoomSetpUserAbs | Input | O | knx:valueTemp |
| knx:dpa.384.52 | TempRoomSetpUserOffset | Input | O | knx:valueTempD |
| knx:dpa.384.53 | ComfortProlongUser | Input | O | knx:trigger |
| knx:dpa.384.54 | ComfortPushbutton | Input | O | knx:trigger |
| knx:dpa.384.55 | HVACModeUser | Input | O | knx:hvacMode |
FB 101: Room Setpoint Manager Temperature Driven
knx:fb.101 [RSMTD]
Defined in: Ch. 7/10/4 §3.5 (KNX Standard v3.0.4)
(NOTE: This Functional Block is in 'beta' status and may be subject to changes)
| DPA | Desc | Direction | Mandatory | DPT |
|---|---|---|---|---|
| knx:dpa.101.51 | TempRoomSetpHeatEff | Output | O | knx:valueTemp |
| knx:dpa.101.52 | TempRoomSetpHeatEffNext | Output | O | knx:temphvacAbsNext |
| knx:dpa.101.53 | TempRoomSetpCoolEff | Output | O | knx:valueTemp |
| knx:dpa.101.54 | TempRoomSetpCoolEffNext | Output | O | knx:temphvacAbsNext |
| knx:dpa.101.55 | StatusTempRoomSetpEff | Output | O | knx:statusRoomSetp |
| knx:dpa.113.52 | TempRoomSetpAbsNext | Input | O | knx:temphvacAbsNext |
| knx:dpa.121.51 | TempRoomSetpTariffShift | Input | O | knx:valueTempD |
| knx:dpa.121.52 | TempRoomSetpLoadShedShift | Input | O | knx:valueTempD |
| knx:dpa.343.51 | WindowStatus | Input | O | knx:windowDoor |
| knx:dpa.384.51 | TempRoomSetpUserAbs | Input | O | knx:valueTemp |
| knx:dpa.384.52 | TempRoomSetpUserOffset | Input | O | knx:valueTempD |
| knx:dpa.384.53 | ComfortProlongUser | Input | O | knx:trigger |
| knx:dpa.396.51 | EnableTempRoomSetpAlt | Input | O | knx:enable |
FB 102: Setpoint Manager Air Quality
knx:fb.102 [SMAQ]
Defined in: Ch. 07/10/04 §3.6
| DPA | Desc | Direction | Mandatory | DPT |
|---|---|---|---|---|
| knx:dpa.102.51 | AQSetpEff | Output | M | knx:valueAirQuality |
| knx:dpa.102.52 | AQSetpUserEff | Output | M | knx:valueAirQuality |
| knx:dpa.102.53 | AQSetpUser | Input | O | knx:valueAirQuality |
FB 103: Setpoint Manager Relative Humidity
knx:fb.103 [SMRH]
Defined in: Ch. 7/10/4 §3.7 (KNX Standard v3.0.4)
(NOTE: This Functional Block is in 'beta' status and may be subject to changes)
| DPA | Desc | Direction | Mandatory | DPT |
|---|---|---|---|---|
| knx:dpa.103.51 | HumRelSetpHumEff | Output | O | knx:valueHumidity |
| knx:dpa.103.52 | HumRelSetpDehumEff | Output | O | knx:valueHumidity |
| knx:dpa.103.53 | HumRelSetpUserEff | Output | O | knx:valueHumidity |
| knx:dpa.103.54 | HumDehumMode | Output | O | knx:humDehumMode |
| knx:dpa.388.51 | RelHumSetpUser | Input | O | knx:valueHumidity |
FB 104: Programme to HVAC-Mode Conversion
knx:fb.104 [PMC]
Defined in: Ch. 07/10/04 §3.2
| DPA | Desc | Direction | Mandatory | DPT |
|---|---|---|---|---|
| knx:dpa.104.51 | HVACMode | Output | M | knx:hvacMode |
| knx:dpa.104.53 | EnableComfort | Output | O | knx:enable |
| knx:dpa.104.54 | ContrMode | Output | O | knx:hvacContrMode |
| knx:dpa.104.55 | BuildingMode | Input | O | knx:buildingMode |
| knx:dpa.104.56 | OccMode | Input | O | knx:occMode |
| knx:dpa.104.57 | ContrModeBO | Input | O | knx:hvacContrMode |
FB 108: HVAC Emergency Source
knx:fb.108 [HVACEMS]
Defined in: Ch. 07/10/04 §3.10
| DPA | Desc | Direction | Mandatory | DPT |
|---|---|---|---|---|
| knx:dpa.108.51 | EmergMode | Output | M | knx:hvacEmergMode |
FB 109: Building/Occ-Mode Source
knx:fb.109 [BOS]
Defined in: Ch. 07/10/04 §3.9
| DPA | Desc | Direction | Mandatory | DPT |
|---|---|---|---|---|
| knx:dpa.109.51 | BuildingMode | Output | O | knx:buildingMode |
| knx:dpa.109.53 | OccMode | Output | O | knx:occMode |
| knx:dpa.109.55 | ContrModeBO | Output | O | knx:hvacContrMode |
FB 116: Position to ON/OFF Converter
knx:fb.116 [POOC]
Defined in: Ch. 07/10/04 §3.11
| DPA | Desc | Direction | Mandatory | DPT |
|---|---|---|---|---|
| knx:dpa.116.51 | ActPosSetpHeatStageA | Input | M | knx:scaling |
| knx:dpa.116.52 | ActPosSetpHeatStageB | Input | M | knx:scaling |
| knx:dpa.116.53 | ActPosSetpCoolStageA | Input | M | knx:scaling |
| knx:dpa.116.54 | ActPosSetpCoolStageB | Input | M | knx:scaling |
| knx:dpa.116.55 | ActStatHeatStageA | Output | O | knx:switch |
| knx:dpa.116.56 | ActStatHeatStageB | Output | O | knx:switch |
| knx:dpa.116.57 | ActStatCoolStageA | Output | O | knx:switch |
| knx:dpa.116.58 | ActStatCoolStageB | Output | O | knx:switch |
| knx:dpa.116.59 | ActStatHeatCool | Output | O | knx:switch |
| knx:dpa.116.60 | Fault | Output | O | knx:bool |
| knx:dpa.116.61 | Overridden | Output | O | knx:bool |
FB 120: Flow Temperature Controller
knx:fb.120 [FTC]
Defined in: Ch. 07/11/02 §2.4
| DPA | Desc | Direction | Mandatory | DPT |
|---|---|---|---|---|
| knx:dpa.120.51 | ChangeOverStatusWater | Input | O | knx:heatpCool |
| knx:dpa.120.52 | TempFlowWaterSetp | Input | M | knx:valueTemp |
| knx:dpa.120.53 | TempFlowWater | Output | M | knx:valueTemp |
| knx:dpa.120.54 | Fault | Output | M | knx:bool |
| knx:dpa.120.55 | CtrlStatus | Output | O | knx:switch |
FB 139: Heat Pump
knx:fb.139
Defined in: Ch. 07/80/02 §2
| DPA | Desc | Direction | Mandatory | DPT |
|---|---|---|---|---|
| knx:dpa.139.51 | HeatPumpMode | Input | M | knx:heatPumpMode |
| knx:dpa.139.52 | TempFlowWaterSetp | Input | O | knx:valueTemp |
| knx:dpa.139.53 | ElectricalPowerLimit | Input | O | knx:valuePower |
| knx:dpa.139.54 | TempOutside | Input | M | knx:valueTemp |
| knx:dpa.139.55 | DHWMode | Input | O | knx:dhwMode |
| knx:dpa.139.56 | TempSetpExtBuffEff | Input | O | knx:valueTemp |
| knx:dpa.139.57 | TempWaterExtBuff | Input | O | knx:valueTemp |
| knx:dpa.139.60 | EnergyEfficiency | Output | M | knx:coefficient |
| knx:dpa.139.61 | HeatPumpModeEff | Output | M | knx:heatPumpMode |
| knx:dpa.139.62 | DHWModeEff | Output | O | knx:dhwMode |
| knx:dpa.139.63 | ErrorHeatPump | Output | O | knx:alarm |
| knx:dpa.139.64 | TempFlowWater | Output | O | knx:valueTemp |
| knx:dpa.139.65 | TempFlowWaterSetpEff | Output | O | knx:valueTemp |
| knx:dpa.139.66 | TempReturnWater | Output | M | knx:valueTemp |
| knx:dpa.139.67 | TempSetpExtBuff | Output | O | knx:valueTemp |
| knx:dpa.139.68 | TempWaterBuff | Output | O | knx:valueTemp |
| knx:dpa.139.69 | TempSrc | Output | O | knx:valueTemp |
| knx:dpa.139.70 | EnergyElectricalTotal | Output | O | knx:activeEnergy |
| knx:dpa.139.71 | EnergyElectricalHeat | Output | O | knx:activeEnergy |
| knx:dpa.139.72 | EnergyElectricalCool | Output | O | knx:activeEnergy |
| knx:dpa.139.73 | EnergyElectricalDHW | Output | O | knx:activeEnergy |
| knx:dpa.139.74 | EnergyThermalTotal | Output | O | knx:activeEnergy |
| knx:dpa.139.75 | EnergyThermalHeat | Output | O | knx:activeEnergy |
| knx:dpa.139.76 | EnergyThermalCool | Output | O | knx:activeEnergy |
| knx:dpa.139.77 | EnergyThermalDHW | Output | O | knx:activeEnergy |
| knx:dpa.139.78 | CurrentElectricalPowerTotal | Output | O | knx:valuePower |
| knx:dpa.139.79 | CurrentThermalPowerTotal | Output | O | knx:valuePower |
| knx:dpa.139.80 | OpHrsCompressor | Output | O | knx:longDeltaTimeSec |
| knx:dpa.139.81 | CountCompressorStarts | Output | O | knx:value2Ucount |
FB 140: Solar Heat Control
knx:fb.140
Defined in: Ch. 07/80/02 §3
| DPA | Desc | Direction | Mandatory | DPT |
|---|---|---|---|---|
| knx:dpa.140.51 | PowerOnOff | Input | M | knx:switch |
| knx:dpa.140.52 | PowerControlSetp | Input | O | knx:scaling |
| knx:dpa.140.60 | PowerControlEff | Output | M | knx:scaling |
| knx:dpa.140.61 | TempSolarCollector | Output | M | knx:valueTemp |
| knx:dpa.140.62 | ThermalPowerHeat | Output | O | knx:valuePower |
| knx:dpa.140.63 | ThermalEnergyHeat | Output | O | knx:activeEnergy |
FB 141: Heating Rod
knx:fb.141
Defined in: Ch. 07/80/02 §4
| DPA | Desc | Direction | Mandatory | DPT |
|---|---|---|---|---|
| knx:dpa.141.51 | LoadOnOff | Input | M | knx:switch |
| knx:dpa.141.52 | LoadControlSetp | Input | O | knx:scaling |
| knx:dpa.141.53 | BufferFull | Input | M | knx:bool |
| knx:dpa.141.60 | LoadControlEff | Output | O | knx:scaling |
| knx:dpa.141.61 | PowerL1 | Output | O | knx:valuePower |
| knx:dpa.141.62 | PowerL2 | Output | O | knx:valuePower |
| knx:dpa.141.63 | PowerL3 | Output | O | knx:valuePower |
| knx:dpa.141.64 | PowerL1L2L3 | Output | O | knx:valuePower |
FB 142: Buffer Storage
knx:fb.142
Defined in: Ch. 07/80/02 §5
| DPA | Desc | Direction | Mandatory | DPT |
|---|---|---|---|---|
| knx:dpa.142.51 | TempWaterSetp | Input | M | knx:valueTemp |
| knx:dpa.142.60 | TempWaterSetpEff | Output | M | knx:valueTemp |
| knx:dpa.142.61 | BufferFull | Output | M | knx:bool |
| knx:dpa.142.62 | TempWaterTop | Output | M | knx:valueTemp |
| knx:dpa.142.63 | TempWater2nd | Output | M | knx:valueTemp |
| knx:dpa.142.64 | TempWater3rd | Output | M | knx:valueTemp |
| knx:dpa.142.65 | TempWater4th | Output | M | knx:valueTemp |
| knx:dpa.142.66 | TempWater5th | Output | M | knx:valueTemp |
FB 146: Auxiliary Heating Demand Percent
knx:fb.146 [HDAUXPER]
Defined in: Ch. 07/14/01 §2.4
| DPA | Desc | Direction | Mandatory | DPT |
|---|---|---|---|---|
| knx:dpa.146.51 | EnergyDemHeatHDAUXPER | Output | M | knx:percentU8 |
FB 151: Heating Demand Transformer Room Temperature
knx:fb.151 [HDTRT]
Defined in: Ch. 07/11/04 §2.6
| DPA | Desc | Direction | Mandatory | DPT |
|---|---|---|---|---|
| knx:dpa.151.51 | TempFlowWaterDemHeatShift | Input | M | knx:valueTempD |
| knx:dpa.151.52 | TempRoomDemAbsHeatMax | Input | M | knx:valueTemp |
| knx:dpa.151.53 | PumpControl | Input | O | knx:switch |
FB 153: Radiator Heating Energy Demand Transformer TU
knx:fb.153 [RHDTTU]
Defined in: Ch. 07/13/02 §3.2
| DPA | Desc | Direction | Mandatory | DPT |
|---|---|---|---|---|
| knx:dpa.153.51 | TempOutside | Input | O | knx:valueTemp |
| knx:dpa.153.52 | ValueEnergyDemRD | Input | O | knx:percentU8 |
| knx:dpa.153.53 | ContrModeAct | Input | O | knx:hvacContrMode |
FB 154: Air Heater Energy Demand Transformer TU
knx:fb.154 [AHDTTU]
Defined in: Ch. 07/13/02 §3.4
| DPA | Desc | Direction | Mandatory | DPT |
|---|---|---|---|---|
| knx:dpa.154.51 | TempOutside | Input | O | knx:valueTemp |
| knx:dpa.154.52 | ValueEnergyDemAH | Input | O | knx:percentU8 |
| knx:dpa.154.53 | ContrModeAct | Input | O | knx:hvacContrMode |
FB 160: Heating Zone Controller
knx:fb.160 [HZC]
Defined in: Ch. 07/11/04 §2.2
| DPA | Desc | Direction | Mandatory | DPT |
|---|---|---|---|---|
| knx:dpa.160.51 | TempFlowWater | Input | O | knx:valueTemp |
| knx:dpa.160.52 | HVACModeAct | Output | O | knx:hvacMode |
| knx:dpa.160.53 | TempRoomSetpHeatAct | Output | O | knx:valueTemp |
| knx:dpa.160.54 | TempReturnWater | Input | O | knx:valueTemp |
| knx:dpa.160.55 | TempFlowWaterHZC | Output | O | knx:valueTemp |
| knx:dpa.160.56 | TempRoomSetpHeatEff | Input | M | knx:valueTemp |
| knx:dpa.160.57 | TempRoomSetpOptimHeatShift | Input | O | knx:valueTempD |
| knx:dpa.160.58 | TempRoom | Input | O | knx:valueTemp |
| knx:dpa.160.59 | WindSpeed | Input | O | knx:valueWsp |
| knx:dpa.160.60 | SunIntensity | Input | O | knx:powerDensity |
| knx:dpa.160.61 | Fault | Output | O | knx:bool |
| knx:dpa.160.62 | StatusMorningBoost | Output | O | knx:bool |
| knx:dpa.160.63 | StatusECO | Output | O | knx:bool |
| knx:dpa.160.64 | SummerMode | Output | O | knx:bool |
FB 169: Heating Demand Transformer Actuator Position
knx:fb.169 [HDTACT]
Defined in: Ch. 07/11/04 §2.5
| DPA | Desc | Direction | Mandatory | DPT |
|---|---|---|---|---|
| knx:dpa.169.51 | TempFlowWaterDemHeatShift | Output | M | knx:valueTempD |
| knx:dpa.169.52 | PumpControl | Output | O | knx:switch |
| knx:dpa.169.53 | ActPosDemAbsHeatMax | Input | M | knx:scaling |
FB 170: Heating Room Demand Manager
knx:fb.170 [HRDM]
Defined in: Ch. 07/11/04 §2.4
| DPA | Desc | Direction | Mandatory | DPT |
|---|---|---|---|---|
| knx:dpa.170.51 | TempRoomDemAbsHeatMax | Output | M | knx:valueTemp |
| knx:dpa.170.52 | ActPosDemAbsHeatMax | Output | M | knx:scaling |
| knx:dpa.170.53 | TempRoomDemAbsHeat | Input | M | knx:valueTemp |
| knx:dpa.170.54 | ActPosDemAbsHeat | Input | M | knx:scaling |
FB 177: Domestic Hot Water Controller
knx:fb.177 [DHWC]
Defined in: Ch. 07/11/03 §2.3
| DPA | Desc | Direction | Mandatory | DPT |
|---|---|---|---|---|
| knx:dpa.177.51 | TempFlowWater | Input | O | knx:valueTemp |
| knx:dpa.177.52 | TempDHWSetpAct | Output | O | knx:valueTemp |
| knx:dpa.177.53 | TempDHWSensorHigh | Output | O | knx:valueTemp |
| knx:dpa.177.54 | TempDHWSensorLow | Output | O | knx:valueTemp |
| knx:dpa.177.55 | TempDHWSetpEff | Input | M | knx:valueTemp |
| knx:dpa.177.56 | DHWModeAct | Output | O | knx:dhwMode |
| knx:dpa.177.57 | TempFlowWaterDHW | Output | O | knx:valueTemp |
| knx:dpa.177.58 | TempDHWSetpOptimShift | Input | O | knx:valueTempD |
| knx:dpa.177.59 | TempDHW | Input | O | knx:valueTemp |
| knx:dpa.177.60 | DHWPush | Input | O | knx:trigger |
| knx:dpa.177.61 | DHWOtherEnergySource | Input | O | knx:bool |
| knx:dpa.177.62 | TempCollectorAct | Input | O | knx:valueTemp |
| knx:dpa.177.63 | Fault | Output | O | knx:bool |
| knx:dpa.177.64 | DHWLoadActive | Output | O | knx:bool |
| knx:dpa.177.65 | LegioProtActive | Output | O | knx:bool |
| knx:dpa.177.66 | DHWPushActive | Output | O | knx:bool |
| knx:dpa.177.67 | OtherEnergySourceActive | Output | O | knx:bool |
| knx:dpa.177.68 | SolarEnergyOnly | Output | O | knx:bool |
| knx:dpa.177.69 | SolarEnergySupport | Output | O | knx:bool |
| knx:dpa.177.70 | TempOptimShiftActive | Output | O | knx:bool |
FB 180: DHW Temperature Sensor
knx:fb.180 [DHWTS]
Defined in: Ch. 07/11/03 §2.6
| DPA | Desc | Direction | Mandatory | DPT |
|---|---|---|---|---|
| knx:dpa.180.51 | TempDHW | Output | M | knx:valueTemp |
FB 187: Collector Temperature Sensor
knx:fb.187 [COLTS]
Defined in: Ch. 07/11/03 §2.7
| DPA | Desc | Direction | Mandatory | DPT |
|---|---|---|---|---|
| knx:dpa.187.51 | TempCollector | Output | M | knx:valueTemp |
FB 210: Auxiliary Cooling Demand Percent
knx:fb.210 [CDAUXPER]
Defined in: Ch. 07/14/01 §2.5
| DPA | Desc | Direction | Mandatory | DPT |
|---|---|---|---|---|
| knx:dpa.210.52 | EnergyDemCoolCDAUXPER | Output | M | knx:percentU8 |
FB 216: Chilled Ceiling Energy Demand Transformer TU
knx:fb.216 [CCDTTU]
Defined in: Ch. 07/13/02 §3.3
| DPA | Desc | Direction | Mandatory | DPT |
|---|---|---|---|---|
| knx:dpa.216.51 | TempOutside | Input | O | knx:valueTemp |
| knx:dpa.216.52 | ValueEnergyDemCC | Input | O | knx:percentU8 |
| knx:dpa.216.53 | ContrModeAct | Input | O | knx:hvacContrMode |
FB 217: Air Cooler Energy Demand Transformer TU
knx:fb.217 [ACDTTU]
Defined in: Ch. 07/13/02 §3.5
| DPA | Desc | Direction | Mandatory | DPT |
|---|---|---|---|---|
| knx:dpa.217.51 | TempOutside | Input | O | knx:valueTemp |
| knx:dpa.217.52 | ValueEnergyDemAC | Input | O | knx:percentU8 |
| knx:dpa.217.53 | ContrModeAct | Input | O | knx:hvacContrMode |
FB 224: Cooling Zone Controller
knx:fb.224 [CZC]
Defined in: Ch. 07/14/02 §4.2
| DPA | Desc | Direction | Mandatory | DPT |
|---|---|---|---|---|
| knx:dpa.224.51 | TempFlowWater | Input | O | knx:valueTemp |
| knx:dpa.224.52 | TempReturnWater | Input | O | knx:valueTemp |
| knx:dpa.224.53 | TempRoomSetpCoolAct | Output | O | knx:valueTemp |
| knx:dpa.224.54 | HVACModeAct | Output | O | knx:hvacMode |
| knx:dpa.224.55 | TempFlowWaterCZC | Output | O | knx:valueTemp |
| knx:dpa.224.56 | TempRoomSetpCoolEff | Input | M | knx:valueTemp |
| knx:dpa.224.57 | TempRoomSetpOptimCoolShift | Input | O | knx:valueTempD |
| knx:dpa.224.58 | TempRoom | Input | O | knx:valueTemp |
| knx:dpa.224.59 | SunIntensity | Input | O | knx:powerDensity |
| knx:dpa.224.60 | WindSpeed | Input | O | knx:valueWsp |
| knx:dpa.224.61 | TempOutside | Input | O | knx:valueTemp |
| knx:dpa.224.62 | Fault | Output | O | knx:bool |
FB 240: Air Handling Unit Controller
knx:fb.240 [AHUC]
Defined in: Ch. 07/14/01 §2.2
| DPA | Desc | Direction | Mandatory | DPT |
|---|---|---|---|---|
| knx:dpa.240.51 | EnergyDemHeatAHUC | Output | O | knx:percentU8 |
| knx:dpa.240.52 | EnergyDemCoolAHUC | Output | O | knx:percentU8 |
| knx:dpa.240.53 | TempRoomSetpHeatEff | Input | M | knx:valueTemp |
| knx:dpa.240.54 | HVACModeAct | Output | O | knx:hvacMode |
| knx:dpa.240.55 | TempRoomSetpAct | Output | O | knx:valueTemp |
| knx:dpa.240.56 | TempRoomSetpCoolEff | Input | M | knx:valueTemp |
| knx:dpa.240.57 | TempRoomSetpOptimHeatShift | Input | O | knx:valueTempD |
| knx:dpa.240.58 | TempRoomSetpOptimCoolShift | Input | O | knx:valueTempD |
| knx:dpa.240.59 | ContrMode | Input | O | knx:hvacContrMode |
| knx:dpa.240.60 | EmergMode | Input | O | knx:hvacEmergMode |
| knx:dpa.240.61 | AQSetpEff | Input | O | knx:valueAirQuality |
| knx:dpa.240.62 | HumRelSetpHumEff | Input | O | knx:valueHumidity |
| knx:dpa.240.63 | HumRelSetpDehumEff | Input | O | knx:valueHumidity |
| knx:dpa.240.64 | TempRoom | Input | O | knx:valueTemp |
| knx:dpa.240.65 | AQRoom | Input | O | knx:valueAirQuality |
| knx:dpa.240.66 | HumRelRoom | Input | O | knx:valueHumidity |
| knx:dpa.240.67 | TempSupplyAir | Input | O | knx:valueTemp |
| knx:dpa.240.68 | AQSupplyAir | Input | O | knx:valueAirQuality |
| knx:dpa.240.69 | HumRelSupplyAir | Input | O | knx:valueHumidity |
| knx:dpa.240.70 | TempOutside | Input | O | knx:valueTemp |
| knx:dpa.240.71 | HumRelOutside | Input | O | knx:valueHumidity |
| knx:dpa.240.72 | WindSpeed | Input | O | knx:valueWsp |
| knx:dpa.240.73 | SunIntensity | Input | O | knx:powerDensity |
| knx:dpa.240.74 | Fault | Output | O | knx:bool |
| knx:dpa.240.75 | FanActive | Output | O | knx:bool |
| knx:dpa.240.76 | ActPosSetpHeatStageA | Output | O | knx:scaling |
| knx:dpa.240.77 | ActPosSetpFreshAir | Output | O | knx:scaling |
| knx:dpa.240.78 | ActPosSetpHeatStageB | Output | O | knx:scaling |
| knx:dpa.240.79 | ActPosSetpCoolStageA | Output | O | knx:scaling |
| knx:dpa.240.80 | ActPosSetpCoolStageB | Output | O | knx:scaling |
FB 262: VAV Control Extract Air
knx:fb.262 [VAVCEA]
Defined in: Ch. 07/13/01 §3.8
| DPA | Desc | Direction | Mandatory | DPT |
|---|---|---|---|---|
| knx:dpa.262.51 | AirFlowMSExtr | Input | M | knx:valueAirFlow |
| knx:dpa.262.52 | EmergMode | Input | O | knx:hvacEmergMode |
| knx:dpa.262.53 | ActPosSetpExtractAir | Output | M | knx:scaling |
FB 320: Outside Temperature Sensor
knx:fb.320 [OTS]
Defined in: Ch. 7/19/20 §3.3 (KNX Standard v3.0.4)
| DPA | Desc | Direction | Mandatory | DPT |
|---|---|---|---|---|
| knx:dpa.320.51 | TempOutside | Output | M | knx:valueTemp |
FB 321: Room Temperature Sensor
knx:fb.321 [RTS]
Defined in: Ch. 7/19/20 §3.1 and Ch. 7/10/1 §3.3 (KNX Standard v3.0.4)
| DPA | Desc | Direction | Mandatory | DPT |
|---|---|---|---|---|
| knx:dpa.321.51 | TempRoom | Output | M | knx:valueTemp |
FB 322: Supply Air Temperature Sensor
knx:fb.322 [SATS]
Defined in: Ch. 07/10/01 §3.4
| DPA | Desc | Direction | Mandatory | DPT |
|---|---|---|---|---|
| knx:dpa.322.51 | TempSupplyAir | Output | M | knx:valueTemp |
| knx:dpa.322.52 | StatusGO | Output | O | knx:statusGen |
FB 323: Return Air Temperature Sensor
knx:fb.323 [RNATS]
Defined in: Ch. 7/10/1 §3.5 (KNX Standard v3.0.4)
(NOTE: This Functional Block is in 'beta' status and may be subject to changes)
| DPA | Desc | Direction | Mandatory | DPT |
|---|---|---|---|---|
| knx:dpa.323.51 | TempReturnAir | Output | M | knx:valueTemp |
| knx:dpa.323.52 | StatusGO | Output | O | knx:statusGen |
FB 324: Flow Water Temperature Sensor
knx:fb.324 [FWTS]
Defined in: Ch. 07/10/01 §3.6
| DPA | Desc | Direction | Mandatory | DPT |
|---|---|---|---|---|
| knx:dpa.324.51 | TempFlowWater | Output | M | knx:valueTemp |
| knx:dpa.324.52 | StatusGO | Output | O | knx:statusGen |
FB 325: Return Water Temperature Sensor
knx:fb.325 [RNWTS]
Defined in: Ch. 07/10/01 §3.7
| DPA | Desc | Direction | Mandatory | DPT |
|---|---|---|---|---|
| knx:dpa.325.51 | TempReturnWater | Output | M | knx:valueTemp |
| knx:dpa.325.52 | StatusGO | Output | O | knx:statusGen |
FB 326: Condenser Flow Water Temperature Sensor
knx:fb.326 [CFWTS]
Defined in: Ch. 07/10/01 §3.21
| DPA | Desc | Direction | Mandatory | DPT |
|---|---|---|---|---|
| knx:dpa.326.51 | TempFlowWaterCond | Output | M | knx:valueTemp |
| knx:dpa.326.52 | StatusGO | Output | O | knx:statusGen |
FB 327: Condenser Return Water Temperature Sensor
knx:fb.327 [CRNWTS]
Defined in: Ch. 07/10/01 §3.22
| DPA | Desc | Direction | Mandatory | DPT |
|---|---|---|---|---|
| knx:dpa.327.51 | TempReturnWaterCond | Output | M | knx:valueTemp |
| knx:dpa.327.52 | StatusGO | Output | O | knx:statusGen |
FB 328: Discharge Temperature Sensor
knx:fb.328 [DATS]
Defined in: Ch. 7/10/1 §3.25 (KNX Standard v3.0.4)
(NOTE: This Functional Block is in 'beta' status and may be subject to changes)
| DPA | Desc | Direction | Mandatory | DPT |
|---|---|---|---|---|
| knx:dpa.328.51 | TempDischargeAir | Output | M | knx:valueTemp |
| knx:dpa.328.52 | StatusGO | Output | O | knx:statusGen |
FB 329: Floor Temperature Sensor
knx:fb.329 [FTS]
Defined in: Ch. 07/19/20 §3.2; 07/10/01 §3.26
| DPA | Desc | Direction | Mandatory | DPT |
|---|---|---|---|---|
| knx:dpa.329.51 | TempFloor | Output | M | knx:valueTemp |
| knx:dpa.329.52 | StatusGO | Output | O | knx:statusGen |
FB 330: Outside AQ Sensor
knx:fb.330 [OAQS]
Defined in: Ch. 07/10/01 §3.13
| DPA | Desc | Direction | Mandatory | DPT |
|---|---|---|---|---|
| knx:dpa.330.51 | AQOutside | Output | M | knx:valueAirQuality |
| knx:dpa.330.52 | StatusGO | Output | O | knx:statusGen |
FB 331: Room AQ Sensor
knx:fb.331 [RAQS]
Defined in: Ch. 7/10/1 §3.14 (KNX Standard v3.0.4)
(NOTE: This Functional Block is in 'beta' status and may be subject to changes)
| DPA | Desc | Direction | Mandatory | DPT |
|---|---|---|---|---|
| knx:dpa.331.51 | AQRoom | Output | M | knx:valueAirQuality |
| knx:dpa.331.52 | StatusGO | Output | O | knx:statusGen |
FB 332: Supply AQ Sensor
knx:fb.332 [SAQS]
Defined in: Ch. 07/10/01 §3.15
| DPA | Desc | Direction | Mandatory | DPT |
|---|---|---|---|---|
| knx:dpa.332.51 | AQSupplyAir | Output | M | knx:valueAirQuality |
| knx:dpa.332.52 | StatusGO | Output | O | knx:statusGen |
FB 333: Return AQ Sensor
knx:fb.333 [RNAQS]
Defined in: Ch. 07/10/01 §3.16
| DPA | Desc | Direction | Mandatory | DPT |
|---|---|---|---|---|
| knx:dpa.333.51 | AQReturnAir | Output | M | knx:valueAirQuality |
| knx:dpa.333.52 | StatusGO | Output | O | knx:statusGen |
FB 336: Outside Relative Humidity Sensor
knx:fb.336 [ORHS]
Defined in: Ch. 07/10/01 §3.19
| DPA | Desc | Direction | Mandatory | DPT |
|---|---|---|---|---|
| knx:dpa.336.51 | HumRelOutside | Output | M | knx:valueHumidity |
| knx:dpa.336.52 | StatusGO | Output | O | knx:statusGen |
FB 337: Room Relative Humidity Sensor
knx:fb.337 [RRHS]
Defined in: Ch. 7/10/1 §3.20 (KNX Standard v3.0.4)
(NOTE: This Functional Block is in 'beta' status and may be subject to changes)
| DPA | Desc | Direction | Mandatory | DPT |
|---|---|---|---|---|
| knx:dpa.337.51 | HumRelRoom | Output | M | knx:valueHumidity |
| knx:dpa.337.52 | StatusGO | Output | O | knx:statusGen |
FB 338: Supply Air Relative Humidity Sensor
knx:fb.338 [SARHS]
Defined in: Ch. 07/10/01 §3.17
| DPA | Desc | Direction | Mandatory | DPT |
|---|---|---|---|---|
| knx:dpa.338.51 | HumRelSupplyAir | Output | M | knx:valueHumidity |
| knx:dpa.338.52 | StatusGO | Output | O | knx:statusGen |
FB 339: Return Air Relative Humidity Sensor
knx:fb.339 [RNARHS]
Defined in: Ch. 07/10/01 §3.18
| DPA | Desc | Direction | Mandatory | DPT |
|---|---|---|---|---|
| knx:dpa.339.51 | HumRelReturnAir | Output | M | knx:valueHumidity |
| knx:dpa.339.52 | StatusGO | Output | O | knx:statusGen |
FB 341: Air Change Over Status Sensor
knx:fb.341 [ACOS]
Defined in: Ch. 07/10/01 §3.23
| DPA | Desc | Direction | Mandatory | DPT |
|---|---|---|---|---|
| knx:dpa.341.51 | ChangeOverStatusAir | Output | M | knx:heatpCool |
| knx:dpa.341.52 | TempSupplyAir | Input | O | knx:valueTemp |
| knx:dpa.341.53 | ChangeOverSwitch | Input | O | knx:switch |
| knx:dpa.341.54 | UserChangeOverMode | Input | O | knx:changeoverMode |
FB 343: Window Switch
knx:fb.343 [WOS]
Defined in: Ch. 7/10/1 §3.11 (KNX Standard v3.0.4)
| DPA | Desc | Direction | Mandatory | DPT |
|---|---|---|---|---|
| knx:dpa.343.51 | WindowStatus | Output | M | knx:windowDoor |
FB 344: Dew Point Status Sensor
knx:fb.344 [DPS]
Defined in: Ch. 7/19/20 §3.4 and Ch. 7/10/1 §3.24 (KNX Standard v3.0.4)
| DPA | Desc | Direction | Mandatory | DPT |
|---|---|---|---|---|
| knx:dpa.344.51 | DewPointStatus | Output | M | knx:alarm |
FB 345: Presence Detector
knx:fb.345 [PRD]
Defined in: Ch. 7/19/20 §3.6 and Ch. 7/10/1 §3.12 (KNX Standard v3.0.4)
| DPA | Desc | Direction | Mandatory | DPT |
|---|---|---|---|---|
| knx:dpa.345.51 | PresenceStatus | Output | M | knx:occupancy |
FB 348: Sun Intensity Sensor
knx:fb.348 [SIS]
Defined in: Ch. 07/10/01 §3.10
| DPA | Desc | Direction | Mandatory | DPT |
|---|---|---|---|---|
| knx:dpa.348.51 | SunIntensity | Output | M | knx:powerDensity |
| knx:dpa.348.52 | StatusGO | Output | O | knx:statusGen |
FB 352: HVAC Valve Actuator Legacy
knx:fb.352 [HVA]
Defined in: Ch. 7/10/3 §3.2.6.1 (KNX Standard v3.0.4)
| DPA | Desc | Direction | Mandatory | DPT |
|---|---|---|---|---|
| knx:dpa.352.51 | ActPosSetpHeatStageA | Input | M | knx:scaling |
| knx:dpa.352.52 | ActPosSetpHeatStageB | Input | O | knx:scaling |
| knx:dpa.352.53 | ActPosSetpCoolStageA | Input | O | knx:scaling |
| knx:dpa.352.54 | ActPosSetpCoolStageB | Input | O | knx:scaling |
| knx:dpa.352.55 | ActPosHeatStageA | Output | O | knx:scaling |
| knx:dpa.352.56 | ActPosHeatStageB | Output | O | knx:scaling |
| knx:dpa.352.57 | ActPosCoolStageA | Output | O | knx:scaling |
| knx:dpa.352.58 | ActPosCoolStageB | Output | O | knx:scaling |
| knx:dpa.352.59 | ActPosHeatCool | Output | O | knx:scaling |
| knx:dpa.352.70 | Fault | Output | O | knx:bool |
| knx:dpa.352.71 | Overridden | Output | O | knx:bool |
| knx:dpa.352.72 | CalibrationMode | Output | O | knx:bool |
| knx:dpa.352.73 | ValveKick | Output | O | knx:bool |
FB 353: HVAC ON/OFF Actuator
knx:fb.353 [HOOA]
Defined in: Ch. 07/10/03 §3.7
| DPA | Desc | Direction | Mandatory | DPT |
|---|---|---|---|---|
| knx:dpa.353.51 | ActStatSetpHeatStageA | Input | M | knx:switch |
| knx:dpa.353.52 | ActStatSetpHeatStageB | Input | M | knx:switch |
| knx:dpa.353.53 | ActStatSetpCoolStageA | Input | M | knx:switch |
| knx:dpa.353.54 | ActStatSetpCoolStageB | Input | M | knx:switch |
| knx:dpa.353.55 | ActStatHeatStageA | Output | O | knx:switch |
| knx:dpa.353.56 | ActStatHeatStageB | Output | O | knx:switch |
| knx:dpa.353.57 | ActStatCoolStageA | Output | O | knx:switch |
| knx:dpa.353.58 | ActStatCoolStageB | Output | O | knx:switch |
| knx:dpa.353.59 | ActStatHeatCool | Output | O | knx:switch |
| knx:dpa.353.60 | Fault | Output | O | knx:bool |
| knx:dpa.353.61 | Overridden | Output | O | knx:bool |
| knx:dpa.353.62 | CalibrationMode | Output | O | knx:bool |
| knx:dpa.353.63 | ValveKick | Output | O | knx:bool |
FB 362: Air Damper Actuator
knx:fb.362 [ADA]
Defined in: Ch. 7/10/3 §3.3.6.1 (KNX Standard v3.0.4)
| DPA | Desc | Direction | Mandatory | DPT |
|---|---|---|---|---|
| knx:dpa.362.51 | ActSetpFreshAir | Input | O | knx:scaling |
FB 372: Fan Actuator
knx:fb.372 [FA]
Defined in: Ch. 7/19/20 §8 and Ch. 7/10/3 §3.4 (KNX Standard v3.0.4)
| DPA | Desc | Direction | Mandatory | DPT |
|---|---|---|---|---|
| knx:dpa.372.51 | ActTargetFanSpeed | Input | M | knx:scaling |
| knx:dpa.372.54 | DisableFan | Input | O | knx:enable |
| knx:dpa.372.55 | ActCurrFanSpeed | Output | O | knx:scaling |
| knx:dpa.372.56 | FanStep | Output | O | knx:fanStage |
| knx:dpa.372.57 | Fault | Output | O | knx:bool |
| knx:dpa.372.58 | Overridden | Output | O | knx:bool |
FB 373: Compressor Actuator
knx:fb.373 [CPA]
Defined in: Ch. 07/10/03 §3.5
| DPA | Desc | Direction | Mandatory | DPT |
|---|---|---|---|---|
| knx:dpa.373.51 | CompressorPosSetp | Input | M | knx:scaling |
| knx:dpa.373.52 | HeatCoolMode | Input | O | knx:heatpCool |
| knx:dpa.373.53 | ElectricalPowerLimitation | Input | O | knx:scaling |
| knx:dpa.373.54 | DisableElPowerLim | Input | O | knx:enable |
| knx:dpa.373.55 | CompressorPosEff | Output | O | knx:scaling |
| knx:dpa.373.56 | Fault | Output | O | knx:bool |
| knx:dpa.373.57 | Overridden | Output | O | knx:bool |
FB 384: User HVAC Room Settings Legacy
knx:fb.384 [UHRS]
Defined in: Ch. 7/10/2 §3.2.6.1 (KNX Standard v3.0.4)
| DPA | Desc | Direction | Mandatory | DPT |
|---|---|---|---|---|
| knx:dpa.384.51 | TempRoomSetpUserAbs | Output | O | knx:valueTemp |
| knx:dpa.384.52 | TempRoomSetpUserOffset | Output | O | knx:valueTempD |
| knx:dpa.384.53 | ComfortProlongUser | Output | O | knx:trigger |
| knx:dpa.384.54 | ComfortPushbutton | Output | O | knx:trigger |
| knx:dpa.384.55 | HVACModeUser | Output | O | knx:hvacMode |
FB 388: User Relative Humidity Setpoint Setting
knx:fb.388 [URHSS]
Defined in: Ch. 07/10/02 §3.7
| DPA | Desc | Direction | Mandatory | DPT |
|---|---|---|---|---|
| knx:dpa.388.51 | RelHumSetpUser | Output | O | knx:valueHumidity |
| knx:dpa.388.52 | HumRelOutside | Input | O | knx:valueHumidity |
| knx:dpa.388.53 | HumRelRoom | Input | O | knx:valueHumidity |
| knx:dpa.388.54 | HumRelReturnAir | Input | O | knx:valueHumidity |
FB 390: User HVAC Display
knx:fb.390 [UHD]
Defined in: Ch. 7/10/2 §3.3 (KNX Standard v3.0.4)
(NOTE: This Functional Block is in 'beta' status and may be subject to changes)
| DPA | Desc | Direction | Mandatory | DPT |
|---|---|---|---|---|
| knx:dpa.100.51 | HVACModeEff | Input | O | knx:hvacMode |
| knx:dpa.100.57 | HVACModeUserEff | Input | O | knx:hvacMode |
| knx:dpa.320.51 | TempOutside | Input | O | knx:valueTemp |
| knx:dpa.321.51 | TempRoom | Input | O | knx:valueTemp |
FB 391: User Presence Switch
knx:fb.391 [UPS]
Defined in: Ch. 7/19/20 §4.2 and Ch. 7/10/2 §3.4 (KNX Standard v3.0.4)
| DPA | Desc | Direction | Mandatory | DPT |
|---|---|---|---|---|
| knx:dpa.391.51 | PresenceStatus | Output | M | knx:occupancy |
FB 392: User Change Over Setting
knx:fb.392 [UCOS]
Defined in: Ch. 07/10/02 §3.10
| DPA | Desc | Direction | Mandatory | DPT |
|---|---|---|---|---|
| knx:dpa.392.51 | UserChangeOverMode | Output | M | knx:changeoverMode |
FB 393: User Fan Speed Setting
knx:fb.393 [UFS]
Defined in: Ch. 7/10/2 §3.5 (KNX Standard v3.0.4)
| DPA | Desc | Direction | Mandatory | DPT |
|---|---|---|---|---|
| knx:dpa.393.51 | FanSpeedUser | Output | M | knx:scaling |
| knx:dpa.393.52 | FanManual | Output | O | knx:enable |
| knx:dpa.393.55 | FanSpeed | Input | O | knx:scaling |
| knx:dpa.393.56 | FanStep | Input | O | knx:value1Ucount |
FB 396: User Enable Alternative Room Temperature Setpoint
knx:fb.396 [UEARTS]
Defined in: Ch. 07/10/02 §3.8
| DPA | Desc | Direction | Mandatory | DPT |
|---|---|---|---|---|
| knx:dpa.396.51 | EnableTempRoomSetpAlt | Output | O | knx:enable |
| knx:dpa.396.52 | StatusTempRoomSetpEff | Input | O | knx:statusRoomSetp |
FB 397: User HVAC Room Settings
knx:fb.397 [UHRS]
Defined in: Ch. 7/19/20 §4.1 and Ch. 7/10/2 §3.3 (KNX Standard v3.0.4)
| DPA | Desc | Direction | Mandatory | DPT |
|---|---|---|---|---|
| knx:dpa.397.51 | HVACModeEff | Input | O | knx:hvacMode |
| knx:dpa.397.52 | HVACModeUserEff | Input | O | knx:hvacMode |
| knx:dpa.397.53 | HVACModeAct | Input | O | knx:hvacMode |
| knx:dpa.397.54 | ComfortProlongEff | Input | O | knx:state |
| knx:dpa.397.55 | TempRoomSetpAct | Input | O | knx:valueTemp |
| knx:dpa.397.56 | TempRoomSetpUserAbsEff | Input | O | knx:valueTemp |
| knx:dpa.397.57 | TempRoomSetpUserOffsetEff | Input | O | knx:valueTempD |
| knx:dpa.397.58 | TempRoomSetpHeatEff | Input | O | knx:valueTemp |
| knx:dpa.397.59 | TempRoomSetpCoolEff | Input | O | knx:valueTemp |
| knx:dpa.397.60 | TempOutside | Input | O | knx:valueTemp |
| knx:dpa.397.61 | TempRoom | Input | O | knx:valueTemp |
| knx:dpa.397.62 | WindowStatusEff | Input | O | knx:windowDoor |
| knx:dpa.397.63 | HeatCoolModeAct | Input | O | knx:heatpCool |
| knx:dpa.397.64 | CombinedStatus_RTSM | Input | O | knx:combinedStatusRTSM |
| knx:dpa.397.65 | CombinedStatus_RTC | Input | O | knx:combinedStatusRTC |
| knx:dpa.397.66 | ActTargetFanSpeedEff | Input | O | knx:scaling |
| knx:dpa.397.67 | FanManualEff | Input | O | knx:enable |
| knx:dpa.397.68 | ActCurrFanSpeed | Input | O | knx:scaling |
| knx:dpa.397.80 | HVACModeUser | Output | O | knx:hvacMode |
| knx:dpa.397.81 | ComfortProlongUser | Output | O | knx:start |
| knx:dpa.397.82 | ComfortPushbutton | Output | O | knx:start |
| knx:dpa.397.83 | TempRoomSetpUserAbs | Output | O | knx:valueTemp |
| knx:dpa.397.84 | TempRoomSetpUserOffset | Output | O | knx:valueTempD |
| knx:dpa.397.85 | TempRoomSetpSetHeat | Output | O | knx:tempRoomSetpSetF16_a4a_ |
| knx:dpa.397.86 | TempRoomSetpSetCool | Output | O | knx:tempRoomSetpSetF16_a4a_ |
| knx:dpa.397.87 | FanSpeedUser | Output | O | knx:scaling |
| knx:dpa.397.88 | FanStepUser | Output | O | knx:fanStage |
| knx:dpa.397.89 | FanManual | Output | O | knx:enable |
FB 398: Room Temperature Setpoint Manager
knx:fb.398 [RTSM]
Defined in: Ch. 7/19/20 §5 and Ch. 7/10/4 §3.4 (KNX Standard v3.0.4)
| DPA | Desc | Direction | Mandatory | DPT |
|---|---|---|---|---|
| knx:dpa.398.51 | HVACMode | Input | M | knx:hvacMode |
| knx:dpa.398.52 | HVACModeNext | Input | O | knx:hvacModeNext |
| knx:dpa.398.53 | HVACModeUser | Input | M | knx:hvacMode |
| knx:dpa.398.54 | ComfortProlongUser | Input | O | knx:start |
| knx:dpa.398.55 | ComfortPushbutton | Input | O | knx:start |
| knx:dpa.398.56 | TempRoomSetpUserAbs | Input | M | knx:valueTemp |
| knx:dpa.398.57 | TempRoomSetpUserOffset | Input | M | knx:valueTempD |
| knx:dpa.398.58 | TempRoomSetpSetHeat | Input | O | knx:tempRoomSetpSetF16_a4a_ |
| knx:dpa.398.59 | TempRoomSetpSetCool | Input | O | knx:tempRoomSetpSetF16_a4a_ |
| knx:dpa.398.60 | TempRoomSetpSetHeatShift | Input | O | knx:tempRoomSetpSetShiftF16_a4a_ |
| knx:dpa.398.61 | TempRoomSetpSetCoolShift | Input | O | knx:tempRoomSetpSetShiftF16_a4a_ |
| knx:dpa.398.62 | WindowStatus | Input | O | knx:windowDoor |
| knx:dpa.398.63 | PresenceStatus | Input | O | knx:occupancy |
| knx:dpa.398.64 | TempOutside | Input | O | knx:valueTemp |
| knx:dpa.398.65 | CombinedStatus_RTC | Input | O | knx:combinedStatusRTC |
| knx:dpa.398.80 | HVACModeEff | Output | O | knx:hvacMode |
| knx:dpa.398.81 | HVACModeUserEff | Output | O | knx:hvacMode |
| knx:dpa.398.82 | HVACModeEffNext | Output | O | knx:hvacModeNext |
| knx:dpa.398.83 | ComfortProlongEff | Output | O | knx:state |
| knx:dpa.398.84 | TempRoomSetpUserAbsEff | Output | O | knx:valueTemp |
| knx:dpa.398.85 | TempRoomSetpHeatEff | Output | O | knx:valueTemp |
| knx:dpa.398.86 | TempRoomSetpUserOffsetEff | Output | O | knx:valueTempD |
| knx:dpa.398.87 | TempRoomSetpCoolEff | Output | O | knx:valueTemp |
| knx:dpa.398.89 | TempRoomSetpSetHeatEff | Output | O | knx:tempRoomSetpSetF16_a4a_ |
| knx:dpa.398.90 | TempRoomSetpSetCoolEff | Output | O | knx:tempRoomSetpSetF16_a4a_ |
| knx:dpa.398.91 | WindowStatusEff | Output | O | knx:windowDoor |
| knx:dpa.398.92 | CombinedStatus_RTSM | Output | O | knx:combinedStatusRTSM |
FB 399: Room Temperature Controller
knx:fb.399 [RTC]
Defined in: Ch. 7/19/20 §6 and Ch. 7/13/1 §3.9 (KNX Standard v3.0.4)
| DPA | Desc | Direction | Mandatory | DPT |
|---|---|---|---|---|
| knx:dpa.399.50 | HVACModeEff | Input | O | knx:hvacMode |
| knx:dpa.399.51 | HVACModeEffNext | Input | O | knx:hvacModeNext |
| knx:dpa.399.52 | TempRoomSetpHeatEff | Input | O | knx:valueTemp |
| knx:dpa.399.53 | TempRoomSetpCoolEff | Input | O | knx:valueTemp |
| knx:dpa.399.54 | TempRoomSetpSetHeatEff | Input | O | knx:tempRoomSetpSetF16_a4a_ |
| knx:dpa.399.55 | TempRoomSetpSetCoolEff | Input | O | knx:tempRoomSetpSetF16_a4a_ |
| knx:dpa.399.56 | TempRoom | Input | M | knx:valueTemp |
| knx:dpa.399.57 | TempOutside | Input | O | knx:valueTemp |
| knx:dpa.399.58 | TempFloor | Input | O | knx:valueTemp |
| knx:dpa.399.59 | SwitchHeat | Input | O | knx:enable |
| knx:dpa.399.60 | SwitchCool | Input | O | knx:enable |
| knx:dpa.399.61 | EnableHeat | Input | O | knx:enableHCstage |
| knx:dpa.399.62 | EnableCool | Input | O | knx:enableHCstage |
| knx:dpa.399.63 | DewPointStatus | Input | O | knx:alarm |
| knx:dpa.399.64 | ChangeOverStatus | Input | O | knx:heatpCool |
| knx:dpa.399.65 | ContrMode | Input | O | knx:hvacContrMode |
| knx:dpa.399.66 | ActCurrPosHeatStageA | Input | O | knx:scaling |
| knx:dpa.399.67 | ActCurrPosHeatStageB | Input | O | knx:scaling |
| knx:dpa.399.68 | ActCurrPosCoolStageA | Input | O | knx:scaling |
| knx:dpa.399.69 | ActCurrPosCoolStageB | Input | O | knx:scaling |
| knx:dpa.399.70 | CombinedStatus_HVA_HeatA | Input | O | knx:combinedStatusHVA |
| knx:dpa.399.71 | CombinedStatus_HVA_HeatB | Input | O | knx:combinedStatusHVA |
| knx:dpa.399.72 | CombinedStatus_HVA_CoolA | Input | O | knx:combinedStatusHVA |
| knx:dpa.399.73 | CombinedStatus_HVA_CoolB | Input | O | knx:combinedStatusHVA |
| knx:dpa.399.74 | FanSpeedUser | Input | O | knx:scaling |
| knx:dpa.399.75 | FanStepUser | Input | O | knx:fanStage |
| knx:dpa.399.76 | FanManual | Input | O | knx:enable |
| knx:dpa.399.77 | ActCurrentFanSpeed | Input | O | knx:scaling |
| knx:dpa.399.78 | CombinedStatus_FA | Input | O | knx:statusGen |
| knx:dpa.399.100 | HVACModeAct | Output | M | knx:hvacMode |
| knx:dpa.399.101 | TempRoomSetpAct | Output | M | knx:valueTemp |
| knx:dpa.399.102 | ActTargetPosHeatStageA | Output | O | knx:scaling |
| knx:dpa.399.103 | ActTargetPosHeatStageB | Output | O | knx:scaling |
| knx:dpa.399.104 | ActTargetPosCoolStageA | Output | O | knx:scaling |
| knx:dpa.399.105 | ActTargetPosCoolStageB | Output | O | knx:scaling |
| knx:dpa.399.106 | ContrModeSecondary | Output | O | knx:hvacContrMode |
| knx:dpa.399.107 | EnableHeatEff | Output | O | knx:enable |
| knx:dpa.399.108 | EnableCoolEff | Output | O | knx:enable |
| knx:dpa.399.109 | HeatCoolModeAct | Output | O | knx:heatpCool |
| knx:dpa.399.110 | CombinedStatus_RTC | Output | O | knx:combinedStatusRTC |
| knx:dpa.399.111 | ContrModeAct | Output | O | knx:hvacContrMode |
| knx:dpa.399.112 | ActTargetFanSpeed | Output | O | knx:scaling |
| knx:dpa.399.201 | FanManualEff | Output | O | knx:enable |
FB 400: HVAC Valve Actuator
knx:fb.400 [HVA]
Defined in: Ch. 7/19/20 §7 and Ch. 7/10/3 §3.2 (KNX Standard v3.0.4)
| DPA | Desc | Direction | Mandatory | DPT |
|---|---|---|---|---|
| knx:dpa.400.50 | ActTargetPos | Input | M | knx:scaling |
| knx:dpa.400.51 | ForcedPosition | Input | O | knx:scaling |
| knx:dpa.400.52 | ForcedPositionEnable | Input | O | knx:enable |
| knx:dpa.400.60 | ActCurrPos | Output | O | knx:scaling |
| knx:dpa.400.70 | Fault | Output | O | knx:bool |
| knx:dpa.400.71 | Overridden | Output | O | knx:bool |
| knx:dpa.400.72 | CalibrationMode | Output | O | knx:bool |
| knx:dpa.400.73 | ValveKick | Output | O | knx:bool |
| knx:dpa.400.74 | CombinedStatus_HVA | Output | O | knx:combinedStatusHVA |
FB 403: Scene Sensor
knx:fb.403 [SCS]
Defined in: Ch. 7/1/2 §3.1.6.1 (KNX Standard v3.0.4)
| DPA | Desc | Direction | Mandatory | DPT |
|---|---|---|---|---|
| knx:dpa.403.61 | NumberedSceneControl | Output | O | knx:sceneControl |
| knx:dpa.403.62 | BinarySceneRecall | Output | O | knx:sceneAB |
| knx:dpa.403.63 | BinarySceneTeachIn | Output | O | knx:sceneAB |
| knx:dpa.403.64 | SceneNumber | Output | O | knx:sceneNumber |
FB 406: Timed Sensor
knx:fb.406 [TS]
Defined in: Ch. 7/1/2 §3.4 (KNX Standard v3.0.4)
| DPA | Desc | Direction | Mandatory | DPT |
|---|---|---|---|---|
| knx:dpa.406.51 | TimedStartStop | Output | M | knx:start |
| knx:dpa.406.52 | OnOffOut | Output | O | knx:switch |
| knx:dpa.406.61 | OnOffIn | Input | O | knx:switch |
| knx:dpa.406.62 | TimedMode | Input | O | knx:state |
FB 409: Indoor Brightness Sensor
knx:fb.409 [IBS]
Defined in: Ch. 7/20/1 §3.2 (KNX Standard v3.0.4)
| DPA | Desc | Direction | Mandatory | DPT |
|---|---|---|---|---|
| knx:dpa.409.51 | Room Illumination | Output | M | knx:valueLux |
FB 410: Indoor Luminance Sensor
knx:fb.410 [ILS]
Defined in: Ch. 07/20/01 §3.3; 07/20/01 Supp.1 §4
| DPA | Desc | Direction | Mandatory | DPT |
|---|---|---|---|---|
| knx:dpa.410.51 | Indoor Luminance | Output | M | knx:valueLuminance |
FB 414: Movement Detector for Lighting
knx:fb.414 [MDL]
Defined in: Ch. 7/20/1 §2 (KNX Standard v3.0.4)
| DPA | Desc | Direction | Mandatory | DPT |
|---|---|---|---|---|
| knx:dpa.414.51 | Switch OnOff | Output | O | knx:switch |
| knx:dpa.414.52 | Timed StartStop | Output | O | knx:start |
| knx:dpa.414.60 | Info OnOff | Input | O | knx:switch |
| knx:dpa.414.61 | Enable | Input | O | knx:enable |
| knx:dpa.414.62 | Brightness External | Input | O | knx:valueLux |
| knx:dpa.414.63 | Movement Trigger | Input | O | knx:start |
FB 417: Light Switching Actuator Basic
knx:fb.417 [LSAB]
Defined in: Ch. 7/20/2 §2.7.1 (KNX Standard v3.0.4)
| DPA | Desc | Direction | Mandatory | DPT |
|---|---|---|---|---|
| knx:dpa.417.51 | InfoOnOff | Output | O | knx:switch |
| knx:dpa.417.52 | SwitchOnOff | Input | M | knx:switch |
| knx:dpa.417.53 | ActuatorStatus | Output | O | knx:statusLightingActuator |
| knx:dpa.417.54 | ControlModeEff | Output | O | knx:lightControlMode |
| knx:dpa.417.55 | ActuatorErrorInfo | Output | O | knx:lightActuatorErrorInfo |
| knx:dpa.417.56 | InfoOnOffFromDimmingActuator | Input | O | knx:switch |
| knx:dpa.417.60 | SwitchOnOffControlCmd | Input | O | knx:switch |
| knx:dpa.417.61 | SwitchOnOffForced | Input | O | knx:switchControl |
| knx:dpa.417.63 | NightMode | Input | O | knx:enable |
| knx:dpa.417.69 | LockDevice | Input | O | knx:enable |
| knx:dpa.417.71 | TimedStartStop | Input | O | knx:start |
| knx:dpa.417.72 | SceneNumber | Input | O | knx:sceneNumber |
| knx:dpa.417.73 | NumberedSceneControl | Input | O | knx:sceneControl |
| knx:dpa.417.74 | ControlModeUser | Input | O | knx:lightControlMode |
FB 418: Light Dimming Actuator Basic
knx:fb.418 [LDAB]
Defined in: Ch. 7/20/2 §3.6.1 (KNX Standard v3.0.4)
| DPA | Desc | Direction | Mandatory | DPT |
|---|---|---|---|---|
| knx:dpa.418.51 | InfoOnOff | Output | O | knx:switch |
| knx:dpa.418.52 | ActualDimmingValue | Output | O | knx:scaling |
| knx:dpa.418.53 | ActuatorStatus | Output | O | knx:statusLightingActuator |
| knx:dpa.418.54 | ControlModeEff | Output | O | knx:lightControlMode |
| knx:dpa.418.55 | ActuatorErrorInfo | Output | O | knx:lightActuatorErrorInfo |
| knx:dpa.418.56 | DetectedLoadType | Output | O | knx:loadTypeDetected |
| knx:dpa.418.57 | OverloadDetection | Output | O | knx:alarm |
| knx:dpa.418.58 | LoadFailedDetection | Output | O | knx:alarm |
| knx:dpa.418.60 | SwitchOnOffControlCmd | Input | O | knx:switch |
| knx:dpa.418.61 | SwitchOnOffForced | Input | O | knx:switchControl |
| knx:dpa.418.62 | SwitchOnOff | Input | M | knx:switch |
| knx:dpa.418.63 | NightMode | Input | O | knx:enable |
| knx:dpa.418.64 | RelSetvalueControlCmd | Input | O | knx:controlDimming |
| knx:dpa.418.65 | AbsSetvalueControlCmd | Input | O | knx:scaling |
| knx:dpa.418.66 | FadeToControlCmd | Input | O | knx:scalingSpeed |
| knx:dpa.418.67 | RelDimmingSpeed | Input | O | knx:timePeriod100MSec |
| knx:dpa.418.68 | RelSetvalueControl | Input | M | knx:controlDimming |
| knx:dpa.418.69 | LockDevice | Input | O | knx:enable |
| knx:dpa.418.70 | AbsSetvalueControl | Input | M | knx:scaling |
| knx:dpa.418.71 | TimedStartStop | Input | O | knx:start |
| knx:dpa.418.72 | SceneNumber | Input | O | knx:sceneNumber |
| knx:dpa.418.73 | NumberedSceneControl | Input | O | knx:sceneControl |
| knx:dpa.418.74 | ControlModeUser | Input | O | knx:lightControlMode |
FB 420: Light Dimming Sensor Basic
knx:fb.420 [LDSB]
Defined in: Ch. 7/20/1 §1.2.7.4 (KNX Standard v3.0.4)
| DPA | Desc | Direction | Mandatory | DPT |
|---|---|---|---|---|
| knx:dpa.420.53 | InfoOnOff | Input | O | knx:switch |
| knx:dpa.420.55 | ActualDimmingValue | Input | O | knx:scaling |
| knx:dpa.420.61 | SwitchOnOff | Output | M | knx:switch |
| knx:dpa.420.62 | RelSetvalueControl | Output | O | knx:controlDimming |
| knx:dpa.420.63 | AbsSetvalueControl | Output | O | knx:scaling |
| knx:dpa.420.65 | TimedStartStop | Output | O | knx:start |
FB 421: Light Switching Sensor Basic
knx:fb.421 [LSSB]
Defined in: Ch. 7/20/1 §1.1.7.2 (KNX Standard v3.0.4)
| DPA | Desc | Direction | Mandatory | DPT |
|---|---|---|---|---|
| knx:dpa.421.53 | InfoOnOff | Input | O | knx:switch |
| knx:dpa.421.61 | SwitchOnOff | Output | M | knx:switch |
| knx:dpa.421.65 | TimedStartStop | Output | O | knx:start |
FB 422: Colour Actuator xyY
knx:fb.422 [CAXYY]
Defined in: Ch. 7/20/2 §7.2.1 (KNX Standard v3.0.5)
| DPA | Desc | Direction | Mandatory | DPT |
|---|---|---|---|---|
| knx:dpa.422.51 | InfoOnOff | Output | O | knx:switch |
| knx:dpa.422.52 | ActualDimmingValue | Output | O | knx:scaling |
| knx:dpa.422.56 | CurrentColour_xyY | Output | O | knx:colourxyY |
| knx:dpa.422.57 | CurrentColour_xyY_OutOfRange | Output | O | knx:bool |
| knx:dpa.422.62 | SwitchOnOff | Input | M | knx:switch |
| knx:dpa.422.68 | RelativeSetvalueControl | Input | M | knx:controlDimming |
| knx:dpa.422.70 | AbsoluteSetvalueControl | Input | M | knx:scaling |
| knx:dpa.422.71 | TimedStartStop | Input | O | knx:start |
| knx:dpa.422.76 | ColourSet_xyY | Input | M | knx:colourxyY |
| knx:dpa.422.77 | ColourRelativeControl_xyY | Input | O | knx:relativeControlxyY |
| knx:dpa.422.78 | ColourTransition_xyY | Input | O | knx:colourTransitionxyY |
FB 423: Colour Actuator RGBW HSVW
knx:fb.423 [CARGBWHSVW]
Defined in: Ch. 7/20/2 §5.7.1 (KNX Standard v3.0.4)
| DPA | Desc | Direction | Mandatory | DPT |
|---|---|---|---|---|
| knx:dpa.423.51 | CombinedSwitchOnOff | Input | M | knx:switch |
| knx:dpa.423.52 | ColourSetRGB | Input | M | knx:colourRGB |
| knx:dpa.423.53 | ColourRelativeControlRGB | Input | O | knx:relativeControlRGB |
| knx:dpa.423.54 | ColourSetRGBW | Input | O | knx:colourRGBW |
| knx:dpa.423.55 | ColourRelativeControlRGBW | Input | O | knx:relativeControlRGBW |
| knx:dpa.423.56 | SwitchOnOffRed | Input | O | knx:switch |
| knx:dpa.423.57 | RelativeSetValueControlRed | Input | O | knx:controlDimming |
| knx:dpa.423.58 | AbsoluteSetValueControlRed | Input | O | knx:scaling |
| knx:dpa.423.59 | SwitchOnOffGreen | Input | O | knx:switch |
| knx:dpa.423.60 | RelativeSetValueControlGreen | Input | O | knx:controlDimming |
| knx:dpa.423.61 | AbsoluteSetValueControlGreen | Input | O | knx:scaling |
| knx:dpa.423.62 | SwitchOnOffBlue | Input | O | knx:switch |
| knx:dpa.423.63 | RelativeSetValueControlBlue | Input | O | knx:controlDimming |
| knx:dpa.423.64 | AbsoluteSetValueControlBlue | Input | O | knx:scaling |
| knx:dpa.423.65 | SwitchOnOffWhite | Input | O | knx:switch |
| knx:dpa.423.66 | RelativeSetValueControlWhite | Input | O | knx:controlDimming |
| knx:dpa.423.67 | AbsoluteSetValueControlWhite | Input | O | knx:scaling |
| knx:dpa.423.68 | ColourSetHSV | Input | O | knx:colourHSV |
| knx:dpa.423.69 | ColourRelativeControlHSV | Input | O | knx:relativeControlHSV |
| knx:dpa.423.70 | ColourSetHSVW | Input | O | knx:colourHSVW |
| knx:dpa.423.71 | ColourRelativeControlHSVW | Input | O | knx:relativeControlHSVW |
| knx:dpa.423.72 | RelativeSetValueControlHue | Input | O | knx:controlDimming |
| knx:dpa.423.73 | AbsoluteSetValueControlHue | Input | O | knx:angle |
| knx:dpa.423.74 | RelativeSetValueControlSat | Input | O | knx:controlDimming |
| knx:dpa.423.75 | AbsoluteSetValueControlSat | Input | O | knx:scaling |
| knx:dpa.423.76 | RelativeSetValueControlVal | Input | O | knx:controlDimming |
| knx:dpa.423.77 | AbsoluteSetValueControlVal | Input | O | knx:scaling |
| knx:dpa.423.80 | CombinedInfoOnOff | Output | M | knx:switch |
| knx:dpa.423.81 | CurrentColourRGB | Output | O | knx:colourRGB |
| knx:dpa.423.82 | CurrentColourRGBW | Output | O | knx:colourRGBW |
| knx:dpa.423.83 | ActualDimmingValueRed | Output | O | knx:scaling |
| knx:dpa.423.84 | ActualDimmingValueGreen | Output | O | knx:scaling |
| knx:dpa.423.85 | ActualDimmingValueBlue | Output | O | knx:scaling |
| knx:dpa.423.86 | ActualDimmingValueWhite | Output | O | knx:scaling |
| knx:dpa.423.87 | CurrentColourHSV | Output | O | knx:colourHSV |
| knx:dpa.423.88 | CurrentColourHSVW | Output | O | knx:colourHSVW |
FB 424: Colour Setting Sensor RGB(W)
knx:fb.424 [CSSRGB]
Defined in: Ch. 7/20/1 §1.4.9 (KNX Standard v3.0.4)
| DPA | Desc | Direction | Mandatory | DPT |
|---|---|---|---|---|
| knx:dpa.424.51 | CombinedSwitchOnOff | Output | M | knx:switch |
| knx:dpa.424.52 | ColourSetRGB | Output | M | knx:colourRGB |
| knx:dpa.424.53 | Colour_RC_RGB | Output | O | knx:relativeControlRGB |
| knx:dpa.424.54 | ColourSetRGBW | Output | O | knx:colourRGBW |
| knx:dpa.424.55 | Colour_RC_RGBW | Output | O | knx:relativeControlRGBW |
| knx:dpa.424.80 | CombinedInfoOnOff | Input | O | knx:switch |
| knx:dpa.424.81 | CurrentColourRGB | Input | O | knx:colourRGB |
| knx:dpa.424.82 | CurrentColourRGBW | Input | O | knx:colourRGBW |
FB 425: Colour Setting Sensor xyY
knx:fb.425 [CSSXYY]
Defined in: Ch. 7/20/1 §1.5.7.1 (KNX Standard v3.0.4)
| DPA | Desc | Direction | Mandatory | DPT |
|---|---|---|---|---|
| knx:dpa.425.50 | Colour_Set_xyY | Output | M | knx:colourxyY |
| knx:dpa.425.51 | Colour_RelativeControl_xyY | Output | O | knx:relativeControlxyY |
| knx:dpa.425.52 | Colour_Transition_xyY | Output | O | knx:colourTransitionxyY |
| knx:dpa.425.53 | CurrentColourxyY | Input | O | knx:colourxyY |
FB 426: Colour Temperature Setting Sensor
knx:fb.426 [CTSS]
Defined in: Ch. 7/20/1 §1.3.8.1 (KNX Standard v3.0.4)
| DPA | Desc | Direction | Mandatory | DPT |
|---|---|---|---|---|
| knx:dpa.426.51 | RelativeSetvalueControlColourTemperature | Output | O | knx:controlDimming |
| knx:dpa.426.52 | AbsoluteColourTemperatureControl | Output | O | knx:absoluteColourTemperature |
| knx:dpa.426.53 | RelativeBrightnessRelativeColourTemperatureControl | Output | O | knx:brightnessColourTemperatureControl |
| knx:dpa.426.54 | BrightnessColourTemperatureTransition | Output | O | knx:brightnessColourTemperatureTransition |
| knx:dpa.426.80 | CurrentColourTemperature | Input | O | knx:absoluteColourTemperature |
FB 427: Colour Temperature Actuator
knx:fb.427 [CTA]
Defined in: Ch. 7/20/2 §3.6.1 (KNX Standard v3.0.4)
| DPA | Desc | Direction | Mandatory | DPT |
|---|---|---|---|---|
| knx:dpa.427.51 | InfoOnOff | Output | O | knx:switch |
| knx:dpa.427.52 | ActualDimmingValue | Output | O | knx:scaling |
| knx:dpa.427.62 | SwitchOnOff | Input | M | knx:switch |
| knx:dpa.427.68 | RelSetvalueControl | Input | M | knx:controlDimming |
| knx:dpa.427.69 | LockDevice | Input | O | knx:enable |
| knx:dpa.427.70 | AbsSetvalueControl | Input | M | knx:scaling |
| knx:dpa.427.71 | TimedStartStop | Input | O | knx:start |
| knx:dpa.427.72 | SceneNumber | Input | O | knx:sceneNumber |
| knx:dpa.427.75 | CurrentColourTemperature | Output | O | knx:absoluteColourTemperature |
| knx:dpa.427.76 | CurrentColourTemperatureOutofRange | Output | O | knx:bool |
| knx:dpa.427.80 | RelativeSetvalueControlColourTemperature | Input | M | knx:controlDimming |
| knx:dpa.427.81 | AbsoluteColourTemperatureControl | Input | M | knx:absoluteColourTemperature |
| knx:dpa.427.82 | RelativeBrightnessRelativeColourTemperatureControl | Input | O | knx:brightnessColourTemperatureControl |
| knx:dpa.427.83 | BrightnessColourTemperatureTransition | Input | O | knx:brightnessColourTemperatureTransition |
FB 440: DALI Proxy Basic Light Application
knx:fb.440 [DPBLA]
Defined in: Ch. 7/20/3 §2 (KNX Standard v3.0.4)
| DPA | Desc | Direction | Mandatory | DPT |
|---|---|---|---|---|
| knx:dpa.440.51 | InfoOnOff | Output | O | knx:switch |
| knx:dpa.440.52 | ActualDimmingValue | Output | O | knx:scaling |
| knx:dpa.440.61 | SwitchOnOffForced | Input | O | knx:switchControl |
| knx:dpa.440.62 | SwitchOnOff | Input | M | knx:switch |
| knx:dpa.440.68 | RelSetvalueControl | Input | M | knx:controlDimming |
| knx:dpa.440.69 | LockDevice | Input | O | knx:enable |
| knx:dpa.440.70 | AbsSetvalueControl | Input | M | knx:scaling |
| knx:dpa.440.71 | TimedStartStop | Input | O | knx:start |
| knx:dpa.440.80 | StatusControlGearDALIchannel | Output | O | knx:alarm |
| knx:dpa.440.81 | StatusLampDALIchannel | Output | O | knx:alarm |
FB 443: DALI Emergency Light Monitoring
knx:fb.443 [DELM]
Defined in: Ch. 7/20/3 §5.6 (KNX Standard v3.0.4)
| DPA | Desc | Direction | Mandatory | DPT |
|---|---|---|---|---|
| knx:dpa.443.151 | Converter Test Control | Input | O | knx:converterTestControl |
| knx:dpa.443.152 | Converter Control | Input | O | knx:converterControl |
| knx:dpa.443.153 | Set Emergency Level | Input | O | knx:scaling |
| knx:dpa.443.154 | Converter Data Request | Input | O | knx:converterDataRequest |
| knx:dpa.443.157 | Converter Status | Output | O | knx:converterStatus |
| knx:dpa.443.158 | Converter Test Result | Output | O | knx:converterTestResult |
| knx:dpa.443.159 | Battery Info | Output | O | knx:batteryInfo |
| knx:dpa.443.160 | Converter FT Info | Output | O | knx:converterTestInfo |
| knx:dpa.443.161 | Converter DT Info | Output | O | knx:converterTestInfo |
| knx:dpa.443.162 | Converter PT Info | Output | O | knx:converterTestInfo |
| knx:dpa.443.163 | Converter Info | Output | O | knx:converterInfo |
FB 800: Sunblind Actuator Basic
knx:fb.800 [SAB]
Defined in: Ch. 7/50/2 §2.5.2.1 (KNX Standard v3.0.4)
| DPA | Desc | Direction | Mandatory | DPT |
|---|---|---|---|---|
| knx:dpa.800.51 | InfoMoveUpDown | Output | O | knx:upDown |
| knx:dpa.800.56 | CurrentAbsolutePositionSlat Percentage | Output | O | knx:scaling |
| knx:dpa.800.65 | MoveUpDownForced | Input | O | knx:direction1Control |
| knx:dpa.800.70 | DedicatedStop | Input | O | knx:trigger |
| knx:dpa.800.71 | SetAbsPosBlindsPercentage | Input | O | knx:scaling |
| knx:dpa.800.72 | SetAbsPosSlatsPercentage | Input | O | knx:scaling |
| knx:dpa.800.75 | NumberedSceneControl | Input | O | knx:sceneControl |
| knx:dpa.800.76 | WindAlarm | Input | O | knx:alarm |
| knx:dpa.800.77 | FrostAlarm | Input | O | knx:alarm |
| knx:dpa.800.78 | RainAlarm | Input | O | knx:alarm |
| knx:dpa.800.79 | SetAbsPositionBlindsLength | Input | O | knx:lengthmm |
| knx:dpa.800.80 | SetAbsPosSlatsDegrees | Input | O | knx:rotationAngle |
| knx:dpa.800.81 | MoveUpDown | Input | M | knx:upDown |
| knx:dpa.800.82 | StopStepUpDown | Input | M | knx:step |
| knx:dpa.800.83 | PresetPosition | Input | O | knx:sceneAB |
| knx:dpa.800.84 | SceneNumber | Input | O | knx:sceneNumber |
| knx:dpa.800.85 | CurrentAbsolutePositionBlindsPercentage | Output | O | knx:scaling |
| knx:dpa.800.86 | CurrentAbsolutePositionBlindsLength | Output | O | knx:lengthmm |
| knx:dpa.800.87 | CurrentAbsolutePositionSlatsDegrees | Output | O | knx:rotationAngle |
| knx:dpa.800.88 | ValidCurrentAbsolutePosition | Output | O | knx:bool |
FB 801: Shutters and Sunblind Sensor Basic
knx:fb.801 [SSSB]
Defined in: Ch. 7/50/1 §1.5.3.1 (KNX Standard v3.0.4)
| DPA | Desc | Direction | Mandatory | DPT |
|---|---|---|---|---|
| knx:dpa.801.61 | MoveUpDown | Output | M | knx:upDown |
| knx:dpa.801.62 | StopStepUpDown | Output | O | knx:step |
| knx:dpa.801.63 | DedicatedStop | Output | O | knx:trigger |
| knx:dpa.801.65 | SetAbsPosBlinds Percentage | Output | O | knx:scaling |
| knx:dpa.801.66 | SetAbsPosSlatsPercentage | Output | O | knx:scaling |
| knx:dpa.801.68 | SetAbsolutePositionBlindsLength | Output | O | knx:lengthmm |
| knx:dpa.801.69 | Set Absolute Position Slats Degrees | Output | O | knx:rotationAngle |
| knx:dpa.801.80 | InfoMoveUpDown | Input | O | knx:upDown |
FB 802: Wind Sensor
knx:fb.802 [WS]
Defined in: Ch. 7/50/1-S1 §2.5.1 (KNX Standard v3.0.4)
| DPA | Desc | Direction | Mandatory | DPT |
|---|---|---|---|---|
| knx:dpa.802.51 | WindAlarm | Output | M | knx:alarm |
FB 803: Rain Sensor
knx:fb.803 [RS]
Defined in: Ch. 7/50/1-S1 §3.5.1 (KNX Standard v3.0.4)
| DPA | Desc | Direction | Mandatory | DPT |
|---|---|---|---|---|
| knx:dpa.803.51 | RainAlarm | Output | M | knx:alarm |
FB 804: Frost Sensor
knx:fb.804 [FS]
Defined in: Ch. 7/50/1-S1 §4.5.1 (KNX Standard v3.0.4)
| DPA | Desc | Direction | Mandatory | DPT |
|---|---|---|---|---|
| knx:dpa.804.51 | FrostAlarm | Output | M | knx:alarm |
FB 1001: System Clock
knx:fb.1001 [SCLO]
Defined in: Ch. 7/1/1 §1.5.1 (KNX Standard v3.0.4)
| DPA | Desc | Direction | Mandatory | DPT |
|---|---|---|---|---|
| knx:dpa.1001.51 | SystemClockOut | Output | O | knx:dateTime |
| knx:dpa.1001.52 | SystemClockSetting | Input | O | knx:dateTime |
| knx:dpa.1001.53 | RelToGMTOut | Output | O | knx:deltaTimeMin |
| knx:dpa.1001.54 | TimeOut | Output | O | knx:timeOfDay |
| knx:dpa.1001.55 | DateOut | Output | O | knx:date |
| knx:dpa.1001.56 | SystemClockIn | Input | O | knx:dateTime |
| knx:dpa.1001.57 | TimeIn | Input | O | knx:timeOfDay |
| knx:dpa.1001.58 | DateIn | Input | O | knx:date |
| knx:dpa.1001.59 | RelToGMTIn | Input | O | knx:deltaTimeMin |
FB 1002: Alarm Source
knx:fb.1002 [ALSrc]
Defined in: Ch. 07/01/04 §3
| DPA | Desc | Direction | Mandatory | DPT |
|---|---|---|---|---|
| knx:dpa.1002.51 | AlarmInfo | Output | M | knx:alarmInfo |
| knx:dpa.1002.52 | AlarmText | Output | O | knx:string88591 |
| knx:dpa.1002.53 | EnableAlarmInfo | Input | M | knx:enable |
| knx:dpa.1002.54 | EnableAlarmText | Input | O | knx:enable |
| knx:dpa.1002.55 | AlarmAck | Input | O | knx:ack |
| knx:dpa.1002.56 | AlarmReset | Input | O | knx:reset |
| knx:dpa.1002.57 | InAlarm | Output | M | knx:alarm |
FB 1010: Scene Controller
knx:fb.1010 [SCCTRL]
Defined in: Ch. 7/1/3 §2 (KNX Standard v3.0.4)
| DPA | Desc | Direction | Mandatory | DPT |
|---|---|---|---|---|
| knx:dpa.1010.53 | Scene Control | Input | O | knx:sceneControl |
| knx:dpa.1010.54 | Scene Number | Input | O | knx:sceneNumber |
| knx:dpa.1010.55 | Scene AB Activate | Input | O | knx:sceneAB |
| knx:dpa.1010.56 | Scene AB Teach | Input | O | knx:sceneAB |
| knx:dpa.1010.60 | Input Value 1..n | Output | O | knx:void |
| knx:dpa.1010.61 | Output Action 1..n | Output | O | knx:void |
FB 1013: Atmospheric Pressure Sensor
knx:fb.1013 [APS]
Defined in: Ch. 7/1/2 §2.1 (KNX Standard v3.0.4)
| DPA | Desc | Direction | Mandatory | DPT |
|---|---|---|---|---|
| knx:dpa.1013.51 | AtmosphericPressureAbs | Output | M | knx:pressure |
FB 1014: General Purpose Digital Input
knx:fb.1014 [GPDI]
Defined in: Ch. 07/01/05 §2.1
| DPA | Desc | Direction | Mandatory | DPT |
|---|---|---|---|---|
| knx:dpa.1014.51 | DigitalInputValue | Output | M | knx:binaryValue |
| knx:dpa.1014.52 | StatusGO | Output | O | knx:statusGen |
FB 1015: General Purpose Analog Input
knx:fb.1015 [GPAI]
Defined in: Ch. 07/01/05 §2.2
| DPA | Desc | Direction | Mandatory | DPT |
|---|---|---|---|---|
| knx:dpa.1015.51 | AnalogInputValue | Output | M | knx:scaling |
| knx:dpa.1015.52 | StatusGO | Output | O | knx:statusGen |
FB 1016: General Purpose Temperature Sensor
knx:fb.1016 [GPTS]
Defined in: Ch. 07/01/05 §2.3
| DPA | Desc | Direction | Mandatory | DPT |
|---|---|---|---|---|
| knx:dpa.1016.51 | TempValue | Output | M | knx:valueTemp |
| knx:dpa.1016.52 | StatusGO | Output | O | knx:statusGen |
FB 1017: Multi Purpose Input
knx:fb.1017 [MPI]
Defined in: Ch. 07/01/05 §2.4
| DPA | Desc | Direction | Mandatory | DPT |
|---|---|---|---|---|
| knx:dpa.1017.51 | DigitalInputValue | Output | M | knx:binaryValue |
| knx:dpa.1017.52 | AnalogInputValue | Output | M | knx:scaling |
| knx:dpa.1017.53 | TempValue | Output | M | knx:valueTemp |
| knx:dpa.1017.54 | StatusGO | Output | O | knx:statusGen |
FB 1018: General Purpose Digital Output
knx:fb.1018 [GPDO]
Defined in: Ch. 07/01/05 §3.1
| DPA | Desc | Direction | Mandatory | DPT |
|---|---|---|---|---|
| knx:dpa.1018.51 | DigitalOutSetp | Input | M | knx:binaryValue |
| knx:dpa.1018.52 | StatusDigitalOutput | Output | O | knx:binaryValue |
| knx:dpa.1018.53 | StopBlinking | Input | O | knx:trigger |
| knx:dpa.1018.54 | ForcedBlinking | Input | O | knx:enable |
FB 1019: General Purpose Analog Output
knx:fb.1019 [GPAO]
Defined in: Ch. 07/01/05 §3.2
| DPA | Desc | Direction | Mandatory | DPT |
|---|---|---|---|---|
| knx:dpa.1019.51 | AnalogOutSetp | Input | M | knx:scaling |
| knx:dpa.1019.52 | StatusAnalogOutput | Output | O | knx:scaling |
FB 1020: Priority Sensor
knx:fb.1020 [PS]
Defined in: Ch. 7/1/2 §3.2 (KNX Standard v3.0.4)
| DPA | Desc | Direction | Mandatory | DPT |
|---|---|---|---|---|
| knx:dpa.1020.51 | Force | Output | M | knx:switchControl |
FB 1021: Lock Sensor
knx:fb.1021 [LS]
Defined in: Ch. 7/1/2 §3.3 (KNX Standard v3.0.4)
| DPA | Desc | Direction | Mandatory | DPT |
|---|---|---|---|---|
| knx:dpa.1021.100 | Lock | Output | M | knx:enable |
FB 1101: MDC Heat Meter
knx:fb.1101 [M_HEATM]
Defined in: Ch. 7/60/1 §5.1 (KNX Standard v3.0.4)
| DPA | Desc | Direction | Mandatory | DPT |
|---|---|---|---|---|
| knx:dpa.1101.51 | CurrentEnergyConsumption | Output | O | knx:value4Count |
| knx:dpa.1101.52 | CurrentPower | Output | O | knx:power |
| knx:dpa.1101.53 | CurrentVolumeFlow | Output | O | knx:valueVolumeFlow |
| knx:dpa.1101.55 | StatusGO | Output | O | knx:statusGen |
| knx:dpa.1101.70 | TempFlowWater | Output | O | knx:valueTemp |
| knx:dpa.1101.71 | TempReturnWater | Output | O | knx:valueTemp |
| knx:dpa.1101.72 | TempDiffWater | Output | O | knx:valueTempD |
| knx:dpa.1101.128 | ReliabilityOfMeteringData | Output | O | knx:bool |
FB 1102: MDC Heat Cost Allocator
knx:fb.1102 [M_HCA]
Defined in: Ch. 7/60/1 §5.2 (KNX Standard v3.0.4)
| DPA | Desc | Direction | Mandatory | DPT |
|---|---|---|---|---|
| knx:dpa.1102.51 | CurrentEnergyConsumption | Output | O | knx:value4Count |
| knx:dpa.1102.55 | StatusGO | Output | O | knx:statusGen |
| knx:dpa.1102.70 | TempFlowWater | Output | O | knx:valueTemp |
| knx:dpa.1102.71 | TempExternal | Output | O | knx:valueTemp |
| knx:dpa.1102.128 | ReliabilityOfMeteringData | Output | O | knx:bool |
FB 1103: MDC Water Meter
knx:fb.1103 [M_WATERM]
Defined in: Ch. 7/60/1 §5.3 (KNX Standard v3.0.4)
| DPA | Desc | Direction | Mandatory | DPT |
|---|---|---|---|---|
| knx:dpa.1103.51 | CurrentVolumeConsumption | Output | O | knx:value4Count |
| knx:dpa.1103.52 | StatusGO | Output | O | knx:statusGen |
| knx:dpa.1103.53 | CurrentVolumeFlow | Output | O | knx:meteringValue |
| knx:dpa.1103.54 | CurrentVolumeFlow | Output | O | knx:valueVolumeFlow |
| knx:dpa.1103.70 | TempFlowWater | Output | O | knx:valueTemp |
FB 1104: MDC Electricity Meter
knx:fb.1104 [M_ELECM]
Defined in: Ch. 7/60/1 §5.6 (KNX Standard v3.0.4)
| DPA | Desc | Direction | Mandatory | DPT |
|---|---|---|---|---|
| knx:dpa.1104.101 | CurrentEnergyConsumption | Output | O | knx:activeEnergy |
| knx:dpa.1104.102 | CurrentEnergyProduction | Output | O | knx:activeEnergy |
| knx:dpa.1104.122 | StatusGO | Output | O | knx:statusGen |
| knx:dpa.1104.128 | ReliabilityOfMeteringData | Output | O | knx:bool |
| knx:dpa.1104.147 | CurrentActivePowerConsumption | Output | O | knx:power |
| knx:dpa.1104.148 | CurrentActivePowerProduction | Output | O | knx:power |
| knx:dpa.1104.153 | BreakerState | Output | O | knx:mBusBreakerValveState |
FB 1105: MDC Gas Meter
knx:fb.1105 [M_GASM]
Defined in: Ch. 7/60/1 §5.5 (KNX Standard v3.0.4)
| DPA | Desc | Direction | Mandatory | DPT |
|---|---|---|---|---|
| knx:dpa.1105.51 | CurrentVolumeConsumption | Output | O | knx:value4Count |
| knx:dpa.1105.53 | CurrentVolumeFlow | Output | O | knx:valueVolumeFlow |
| knx:dpa.1105.70 | TempFlowGas | Output | O | knx:valueTemp |
| knx:dpa.1105.122 | StatusGO | Output | O | knx:statusGen |
| knx:dpa.1105.128 | ReliabilityOfMeteringData | Output | O | knx:bool |
| knx:dpa.1105.153 | ValveState | Output | O | knx:mBusBreakerValveState |
FB 1106: MDC Breaker
knx:fb.1106 [M_BREAKERM]
Defined in: Ch. 7/60/1 §5.7 (KNX Standard v3.0.4)
| DPA | Desc | Direction | Mandatory | DPT |
|---|---|---|---|---|
| knx:dpa.1106.128 | ReliabilityOfMeteringData | Output | O | knx:bool |
| knx:dpa.1106.153 | BreakerState | Output | O | knx:mBusBreakerValveState |
FB 1107: MDC Valve
knx:fb.1107 [M_VALVEM]
Defined in: Ch. 7/60/1 §5.8 (KNX Standard v3.0.4)
| DPA | Desc | Direction | Mandatory | DPT |
|---|---|---|---|---|
| knx:dpa.1107.128 | ReliabilityOfMeteringData | Output | O | knx:bool |
| knx:dpa.1107.153 | ValveState | Output | O | knx:mBusBreakerValveState |
FB 1110: MDC Generic Meter
knx:fb.1110 [M_GENERICM]
Defined in: Ch. 7/60/1 §5.4 (KNX Standard v3.0.4)
| DPA | Desc | Direction | Mandatory | DPT |
|---|---|---|---|---|
| knx:dpa.1110.51 | CurrentEnergyConsumption | Output | O | knx:value4Count |
| knx:dpa.1110.55 | StatusGO | Output | O | knx:statusGen |
| knx:dpa.1110.128 | ReliabilityOfMeteringData | Output | O | knx:bool |
FB 1250: Inverter PV Control
knx:fb.1250
Defined in: Ch. 7/80/1 §2 (KNX Standard v3.0.4)
| DPA | Desc | Direction | Mandatory | DPT |
|---|---|---|---|---|
| knx:dpa.1250.51 | PowerControlSetp | Input | O | knx:scaling |
| knx:dpa.1250.52 | PowerOnOff | Input | O | knx:switch |
| knx:dpa.1250.60 | PowerDC | Output | O | knx:valuePower |
| knx:dpa.1250.61 | VoltageDC | Output | O | knx:valueElectricPotential |
| knx:dpa.1250.62 | CurrentDC | Output | O | knx:valueElectricCurrent |
FB 1251: Inverter Battery Control
knx:fb.1251
Defined in: Ch. 7/80/1 §3 (KNX Standard v3.0.4)
| DPA | Desc | Direction | Mandatory | DPT |
|---|---|---|---|---|
| knx:dpa.1251.51 | ForceGridCharging | Input | O | knx:bool |
| knx:dpa.1251.52 | DisableGridDischarging | Input | O | knx:bool |
| knx:dpa.1251.53 | CapacityBackup | Input | O | knx:scaling |
| knx:dpa.1251.60 | BatteryOpMode | Output | O | knx:void |
| knx:dpa.1251.61 | StateOfCharge | Output | O | knx:scaling |
| knx:dpa.1251.62 | StateOfHealth | Output | O | knx:scaling |
| knx:dpa.1251.63 | CapacityEnergyEff | Output | O | knx:activeEnergy |
| knx:dpa.1251.64 | PowerEff | Output | O | knx:valuePower |
| knx:dpa.1251.65 | PowerChargeMax | Output | O | knx:valuePower |
| knx:dpa.1251.66 | PowerChargeMin | Output | O | knx:valuePower |
| knx:dpa.1251.67 | DepthOfDischarge | Output | O | knx:scaling |
| knx:dpa.1251.68 | Fault | Output | O | knx:alarm |
| knx:dpa.1251.69 | LoadCyclesCount | Output | O | knx:value4Ucount |
| knx:dpa.1251.70 | TempStorage | Output | O | knx:valueTemp |
| knx:dpa.1251.71 | VoltageDC | Output | O | knx:valueElectricPotential |
FB 1252: DC-AC Inverter Monitor
knx:fb.1252
Defined in: Ch. 7/80/1 §4 (KNX Standard v3.0.4)
| DPA | Desc | Direction | Mandatory | DPT |
|---|---|---|---|---|
| knx:dpa.1252.51 | CurrentDC | Output | O | knx:valueElectricCurrent |
| knx:dpa.1252.52 | PowerDC | Output | O | knx:valuePower |
| knx:dpa.1252.53 | VoltageL1L2 | Output | O | knx:valueElectricPotential |
| knx:dpa.1252.54 | VoltageL2L3 | Output | O | knx:valueElectricPotential |
| knx:dpa.1252.55 | VoltageL3L1 | Output | O | knx:valueElectricPotential |
| knx:dpa.1252.56 | VoltageL1 | Output | O | knx:valueElectricPotential |
| knx:dpa.1252.57 | VoltageL2 | Output | O | knx:valueElectricPotential |
| knx:dpa.1252.58 | VoltageL3 | Output | O | knx:valueElectricPotential |
| knx:dpa.1252.59 | CurrentL1 | Output | O | knx:valueElectricCurrent |
| knx:dpa.1252.60 | CurrentL2 | Output | O | knx:valueElectricCurrent |
| knx:dpa.1252.61 | CurrentL3 | Output | O | knx:valueElectricCurrent |
| knx:dpa.1252.62 | CurrentTotal | Output | O | knx:valueElectricCurrent |
| knx:dpa.1252.63 | MainsFrequency | Output | O | knx:valueFrequency |
| knx:dpa.1252.64 | ActivePowerTotal | Output | O | knx:valuePower |
| knx:dpa.1252.65 | ApparentPowerTotal | Output | O | knx:valueApparentPower |
| knx:dpa.1252.66 | ReactivePowerTotal | Output | O | knx:void |
| knx:dpa.1252.67 | PowerFactor | Output | O | knx:valuePowerFactor |
| knx:dpa.1252.68 | ActiveEnergySummation | Output | O | knx:activeEnergy |
| knx:dpa.1252.69 | TempInverter | Output | O | knx:valueTemp |
FB 1253: PCC Monitor
knx:fb.1253
Defined in: Ch. 7/80/1 §5 (KNX Standard v3.0.4)
| DPA | Desc | Direction | Mandatory | DPT |
|---|---|---|---|---|
| knx:dpa.1253.51 | PowerFeedIn | Output | O | knx:valuePower |
| knx:dpa.1253.52 | PowerConsumption | Output | O | knx:valuePower |
| knx:dpa.1253.53 | PowerEff | Output | O | knx:valuePower |
| knx:dpa.1253.54 | VoltageL1 | Output | O | knx:valueElectricPotential |
| knx:dpa.1253.55 | VoltageL2 | Output | O | knx:valueElectricPotential |
| knx:dpa.1253.56 | VoltageL3 | Output | O | knx:valueElectricPotential |
| knx:dpa.1253.57 | MainsFrequency | Output | O | knx:valueFrequency |
| knx:dpa.1253.58 | CurrentL1 | Output | O | knx:valueElectricCurrent |
| knx:dpa.1253.59 | CurrentL2 | Output | O | knx:valueElectricCurrent |
| knx:dpa.1253.60 | CurrentL3 | Output | O | knx:valueElectricCurrent |
FB 1254: EVSE AC
knx:fb.1254
Defined in: Ch. 7/80/3 §2.2 (KNX Standard v3.0.4)
| DPA | Desc | Direction | Mandatory | DPT |
|---|---|---|---|---|
| knx:dpa.1254.51 | CurrentLimitStation | Input | O | knx:valueElectricCurrent |
| knx:dpa.1254.52 | Active Power Limit | Input | O | knx:valuePower |
| knx:dpa.1254.53 | PhaseSwitching | Input | O | knx:switch |
| knx:dpa.1254.60 | CurrentLimitConnector | Input | O | knx:valueElectricCurrent |
| knx:dpa.1254.61 | ActivePowerLimitConnector | Input | O | knx:valuePower |
| knx:dpa.1254.70 | CurrentLimitEffStation | Output | O | knx:valueElectricCurrent |
| knx:dpa.1254.71 | Failsafe | Output | O | knx:bool |
| knx:dpa.1254.72 | ActivePowerLimitEffStation | Output | O | knx:valuePower |
| knx:dpa.1254.73 | FailsafeCurrentEffStation | Output | O | knx:valueElectricCurrent |
| knx:dpa.1254.74 | FailsafeActivePowerEffStation | Output | O | knx:valuePower |
| knx:dpa.1254.75 | ActivePowerStation | Output | O | knx:valuePower |
| knx:dpa.1254.76 | CurrentL1Station | Output | O | knx:valueElectricCurrent |
| knx:dpa.1254.77 | CurrentL2Station | Output | O | knx:valueElectricCurrent |
| knx:dpa.1254.78 | CurrentL3Station | Output | O | knx:valueElectricCurrent |
| knx:dpa.1254.79 | TempPCBA | Output | O | knx:valueTemp |
| knx:dpa.1254.80 | ErrorCode | Output | O | knx:evseMode3 |
| knx:dpa.1254.81 | PhaseSwitchingEff | Output | O | knx:switch |
| knx:dpa.1254.90 | CurrentLimitEffConnector | Output | O | knx:valueElectricCurrent |
| knx:dpa.1254.91 | FailsafeCurrentEffConnector | Output | O | knx:valueElectricCurrent |
| knx:dpa.1254.92 | ActivePowerLimitEffConnector | Output | O | knx:valuePower |
| knx:dpa.1254.93 | FailsafeActivePowerEffConnector | Output | O | knx:valuePower |
| knx:dpa.1254.94 | ActivePowerConnector | Output | O | knx:valuePower |
| knx:dpa.1254.95 | CurrentL1Connector | Output | O | knx:valueElectricCurrent |
| knx:dpa.1254.96 | CurrentL2Connector | Output | O | knx:valueElectricCurrent |
| knx:dpa.1254.97 | CurrentL3Connector | Output | O | knx:valueElectricCurrent |
| knx:dpa.1254.98 | ControlPilotState | Output | O | knx:evseMode1 |
| knx:dpa.1254.99 | OCPPState | Output | O | knx:evseMode2 |
FB 54001: Siemens Device Function
knx:fb.54001 [SDEVFUN]
(NOTE: This Functional Block is in 'beta' status and may be subject to changes)
| DPA | Desc | Direction | Mandatory | DPT |
|---|---|---|---|---|
| knx:dpa.54001.51 | BatteryLowStatus | Output | O | knx:bool |
| knx:dpa.54001.52 | BatteryLevel | Output | O | knx:scaling |
| knx:dpa.54001.53 | InLinkMargin | Output | O | knx:value1Ucount |